Wyoming generation tracker
As of 16 November 2026. Statuses are as reported to EIA for 31 December 2025 in the EIA-860 2025 data release, the most recent final data. They will be updated when EIA publishes newer data.
Summary
For 2025, developers and utilities reported 17 active proposed generators in Wyoming, totalling 7,206.6 MW, against 12,735.6 MW of existing capacity. Of that, 3,550.5 MW was under construction.
- Onshore Wind Turbine: 4,060.6 MW
- Solar Photovoltaic: 1,427.0 MW
- Batteries: 1,099.0 MW
- Nuclear: 500.0 MW
- Natural Gas Fired Combustion Turbine: 120.0 MW
A further 5 generators (621.1 MW) were reported as indefinitely postponed or cancelled, and are listed separately below. Two existing generators report a planned retirement.
Active proposed generators
| Plant | Generator | Technology | Capacity (MW) | County | Owner or operator | Status | Planned operation | EIA plant ID |
|---|---|---|---|---|---|---|---|---|
| Cowboy Solar II | C2BS | Batteries | 200.0 | Laramie | TGE Wyoming 225, LLC | P | Dec 2027 | 69189 |
| Cowboy Solar II | C2PV | Solar Photovoltaic | 365.0 | Laramie | TGE Wyoming 225, LLC | T | Dec 2027 | 69189 |
| Cowboy Solar I | CLP20 | Solar Photovoltaic | 400.0 | Laramie | Cowboy Solar I | P | Mar 2028 | 68022 |
| Two Rivers Wind Facility | TR1 | Onshore Wind Turbine | 6.1 | Carbon | Two Rivers Wind LLC | L | Oct 2028 | 63972 |
| Cheyenne Prairie Generating Station | 02B | Natural Gas Fired Combustion Turbine | 40.0 | Laramie | Black Hills Service Company LLC | P | Dec 2028 | 57703 |
| Cheyenne Prairie Generating Station | 03A | Natural Gas Fired Combustion Turbine | 40.0 | Laramie | Black Hills Service Company LLC | P | Dec 2028 | 57703 |
| Cheyenne Prairie Generating Station | 03B | Natural Gas Fired Combustion Turbine | 40.0 | Laramie | Black Hills Service Company LLC | P | Dec 2028 | 57703 |
| Cowboy Solar I | CLPBS | Batteries | 400.0 | Laramie | Cowboy Solar I | P | Dec 2028 | 68022 |
| Dutchman Solar generation and BESS | DUTC1 | Solar Photovoltaic | 499.0 | Converse | DUTC bn, LLC | L | Jun 2029 | 68317 |
| Dutchman Solar generation and BESS | DUTC2 | Batteries | 499.0 | Converse | DUTC bn, LLC | L | Jun 2029 | 68317 |
| Rail Tie Wind | CRTW1 | Onshore Wind Turbine | 504.0 | Albany | Repsol Renewables NA | L | Jun 2029 | 64847 |
| Goshen Solar | GS1 | Solar Photovoltaic | 163.0 | Goshen | Goshen Solar, LLC | T | Dec 2030 | 67936 |
| Kemmerer Unit 1 | KU1 | Nuclear | 500.0 | Lincoln | US SFR Owner LLC | L | Dec 2030 | 68635 |
| Chokecherry and Sierra Madre Wind | I-A | Onshore Wind Turbine | 844.2 | Carbon | Power Company of Wyoming LLC | U | Dec 2031 | 58987 |
| Chokecherry and Sierra Madre Wind | I-B | Onshore Wind Turbine | 849.6 | Carbon | Power Company of Wyoming LLC | U | Dec 2031 | 58987 |
| Chokecherry and Sierra Madre Wind | II-A | Onshore Wind Turbine | 1,303.2 | Carbon | Power Company of Wyoming LLC | U | Dec 2032 | 58987 |
| Chokecherry and Sierra Madre Wind | II-B | Onshore Wind Turbine | 553.5 | Carbon | Power Company of Wyoming LLC | U | Dec 2033 | 58987 |
Planned retirements
| Plant | Generator | Technology | Capacity (MW) | Operator | Planned retirement | EIA plant ID |
|---|---|---|---|---|---|---|
| Dave Johnston | 3 | Conventional Steam Coal | 229.5 | PacifiCorp | Dec 2027 | 4158 |
| Elk Basin Gasoline Plant | GEN1 | Other Gases | 1.0 | Contango Oil and Gas | Jan 2026 | 52127 |
How planned coal retirement dates have changed
EIA-860 records, each year, the retirement date that a plant's owner plans for each generator. Comparing the annual editions shows how those plans have moved. Between the 2023 and 2024 editions, 10 Wyoming coal units totalling 3,656.1 MW stopped reporting a planned retirement date: Dave Johnston 1, 2 and 4, Jim Bridger 1 to 4, Naughton 1 and 2, and Wyodak. Only Dave Johnston 3 kept its date, December 2027. Two of the units, Jim Bridger 1 and 2, had been converted to burn natural gas by the 2024 edition.
| Unit | 2019 | 2020 | 2021 | 2022 | 2023 | 2024 | 2025 |
|---|---|---|---|---|---|---|---|
| Dave Johnston 1 | none | none | Dec 2027 | Dec 2027 | Dec 2027 | none | none |
| Dave Johnston 2 | none | none | Dec 2027 | Dec 2027 | Dec 2027 | none | none |
| Dave Johnston 3 | Jan 2027 | Jan 2027 | Dec 2027 | Dec 2027 | Dec 2027 | Dec 2027 | Dec 2027 |
| Dave Johnston 4 | none | none | Dec 2027 | Dec 2027 | Dec 2027 | none | none |
| Jim Bridger 1 | none | none | Dec 2037 | Dec 2037 | Dec 2037 | none | none |
| Jim Bridger 2 | none | none | Dec 2037 | Dec 2037 | Dec 2037 | none | none |
| Jim Bridger 3 | none | none | Dec 2037 | Dec 2037 | Dec 2037 | none | none |
| Jim Bridger 4 | none | none | Dec 2037 | Dec 2037 | Dec 2037 | none | none |
| Naughton 1 | none | none | Dec 2025 | Dec 2025 | Dec 2025 | none | none |
| Naughton 2 | none | none | Dec 2025 | Dec 2025 | Dec 2025 | none | none |
| Naughton 3 | none | none | Dec 2029 | Dec 2029 | Dec 2029 | none | none |
| Wyodak 1 | none | none | Dec 2039 | Dec 2039 | Dec 2039 | none | none |
"None" means that edition reported no planned retirement date for the unit. The table shows the editions from 2019; earlier editions, back to 2001, are in the full history. The only earlier planned dates are for Neil Simpson 5 and Osage 1 to 3, which reported March 2014 in the 2011 to 2013 editions and retired that month. Naughton 3 burned coal until its conversion to natural gas and is included for that reason. A missing date records what the owner reported to EIA; the form does not say why a date was added or removed. Every date shown for 2023, 2024 and 2025 was checked against EIA's own workbook.
Indefinitely postponed or cancelled
These remain in some datasets with a "proposed" status, which can overstate the capacity in development if they are not excluded.
| Plant | Generator | Technology | Capacity (MW) | County | Status | EIA plant ID |
|---|---|---|---|---|---|---|
| Chokecherry and Sierra Madre Wind | I-C | Onshore Wind Turbine | 500.0 | Carbon | IP | 58987 |
| Elk Basin Gasoline Plant | EMGEN | Natural Gas Internal Combustion Engine | 0.7 | Park | IP | 52127 |
| Medicine Bow | 12 | Onshore Wind Turbine | 0.7 | Carbon | CN | 692 |
| Medicine Bow | 13 | Onshore Wind Turbine | 0.7 | Carbon | CN | 692 |
| Uinta Wind | WIND1 | Onshore Wind Turbine | 119.0 | Uinta | IP | 68005 |
Interconnection queue
Before a generator can connect to the grid, its developer must request interconnection from the transmission provider and pass through a series of studies. Berkeley Lab's Queued Up data file gathers these requests from every queue in the country. It lists 400 requests for projects in Wyoming, covering requests through the end of 2025.
| Status | Requests | Capacity (MW) |
|---|---|---|
| Withdrawn | 269 | 62,148.1 |
| Active | 73 | 16,175.3 |
| Operational | 51 | 5,134.0 |
| Suspended | 7 | 2,359.0 |
At the end of 2025, 73 requests for 16,175.3 MW were active: 1.3 times Wyoming's existing capacity of 12,735.6 MW, and 2.2 times the 7,206.6 MW of proposed generators reported to EIA. A queue request is an early step, not a plan to build: 26 of the active requests (5,210.5 MW) had signed an interconnection agreement. Of the 247 Wyoming requests entered in 2020 or earlier, 48 (19%) reached commercial operation and 192 (78%) were withdrawn.
Active requests by technology
| Technology (first resource) | Active requests | Capacity (MW) |
|---|---|---|
| Wind | 32 | 5,692.7 |
| Solar | 23 | 5,490.9 |
| Gas | 11 | 3,062.7 |
| Nuclear | 2 | 1,000.0 |
| Battery | 5 | 929.0 |
Active requests by study phase
| Study phase | Active requests | Capacity (MW) |
|---|---|---|
| IA Executed | 26 | 5,210.5 |
| In Progress (unknown study) | 22 | 3,720.1 |
| Cluster Study | 14 | 3,257.0 |
| Facility Study | 2 | 550.0 |
| System Impact Study | 1 | 350.0 |
When requests are withdrawn
Of the 269 withdrawn requests, only 36 (13%) carry a withdrawal date, almost all of them from PacifiCorp. For those 36, the median time from request to withdrawal was 5.5 years, but so few are dated that the figure cannot be taken to represent Wyoming's queue as a whole.
| Queue operator | Withdrawn requests | With a withdrawal date |
|---|---|---|
| PacifiCorp | 246 | 31 |
| CLPT | 13 | 0 |
| SPP | 3 | 2 |
| PRPA | 2 | 0 |
| PSCo | 2 | 2 |
| CAISO | 1 | 1 |
| MISO | 1 | 0 |
| WAPA-IS | 1 | 0 |
Notes: figures count interconnection requests, not projects; one project can file more than one request, or file in more than one queue. Capacity is the first resource's size, so the storage part of a hybrid project is not added. The active capacity computed here for gas, solar and wind matches the Wyoming totals that Berkeley Lab publishes in the same file. Download: all 400 requests.
Reading this tracker
- Every entry comes from EIA Form 860, as processed by PUDL and checked against EIA's own release. The EIA plant ID links each row to EIA's records.
- Proposed projects and dates are reported by their developers. Many proposed projects are delayed or never built, and planned dates often move.
- Status codes show each generator's status on 31 December 2025, using EIA's definitions: P, planned with regulatory approvals not initiated; L, approvals pending; T, approvals received; U and V, under construction (up to and above half complete); TS, built but not yet in commercial operation; IP, indefinitely postponed; CN, cancelled.
- Battery storage paired with a solar project is listed as its own generator, as EIA reports it.
Download the data: proposed generators, planned retirements.